EN‑268B closed‑loop water corrosion inhibitor is designed for chilled‑water and hot‑water closed systems using ethylene glycol, methanol, ethanol or industrial water as cooling media. It also serves as water‑phase corrosion inhibitor for antifreeze fluids, oil tankers and storage tanks to mitigate water‑line corrosion, and is applicable to air‑conditioning chilled‑water systems.
| Item | Specification |
|---|---|
| Appearance | Colorless to pale‑amber liquid |
| pH (1% solution) | ≥9.0 |
| Density (20℃, g/cm³) | ≥1.10 |
Calculated based on system hold‑up water volume: JQSY engineers recommend one‑time initial dosage of 1500 mg/L upon system commissioning; pre‑filming treatment is not required. During normal operation, add 1.3 times the calculated dosage into the expansion tank according to makeup cooling‑water volume. For preservation application in oil tankers or oil storage tanks, better performance can be achieved when used together with demulsifiers.
JQSY corrosion inhibitor is normally packed in blue plastic drums of 25 kg or 250 kg. Store indoors in cool place. Shelf‑life: 10 months.
EN‑268B Closed‑Loop Water Corrosion Inhibitor is weakly alkaline. Take proper labor protection during operation. Avoid contact with skin and eyes. In case of contact, rinse thoroughly with plenty of clean water.
| Item | Specification |
|---|---|
| Appearance | Colorless to pale‑amber liquid |
| pH (1% solution) | ≥9.0 |
| Density (20℃, g/cm³) | ≥1.10 |
Calculated based on system hold‑up water volume: JQSY engineers recommend one‑time initial dosage of 1500 mg/L upon system commissioning; pre‑filming treatment is not required. During normal operation, add 1.3 times the calculated dosage into the expansion tank according to makeup cooling‑water volume. For preservation application in oil tankers or oil storage tanks, better performance can be achieved when used together with demulsifiers.
JQSY corrosion inhibitor is normally packed in blue plastic drums of 25 kg or 250 kg. Store indoors in cool place. Shelf‑life: 10 months.
EN‑268B Closed‑Loop Water Corrosion Inhibitor is weakly alkaline. Take proper labor protection during operation. Avoid contact with skin and eyes. In case of contact, rinse thoroughly with plenty of clean water.